WT-T203

WT-T203
WT-T203

WT-T203 Three-Phase Smart Energy Meter On-site Calibrator

This Calibrator is designed for on-site error calibration of single and three-phase energy meters. It supports electrical parameter measurement, harmonic analysis, on-site wiring anomaly diagnosis, energy retroactive compensation (billing adjustment), and PT/CT secondary burden measurement.

Product Functions

  • Electrical Parameter Measurement: Measures voltage, current, power (P,Q,S), phase angle, frequency, and power factor.
  • Power Quality Analysis: Includes harmonic measurement and real-time waveform display.
  • Dual-Channel Calibration: Equipped with dual pulse inputs to simultaneously calibrate active and reactive energy; supports concurrent testing of primary and secondary meters. Integrated error testing of the entire metering installation is available via configurable transformer ratios.
  • Wiring Analysis & Energy Recovery: Analyzes on-site wiring errors, displays vector diagrams, and calculates real-time energy retroactive compensation.
  • Clock Error Verification: Calibrates the daily timing error of the energy meter’s internal clock.
  • Smart Constant & Energy Comparison: Features intelligent pulse constant verification and energy accumulation comparison.
  • Environmental Monitoring: Measures on-site temperature and humidity.
  • Data Acquisition: Supports reading and retrieval of data stored within the energy meter.
  • Data Management: Enables storage, retrieval, review of historical data, and re-measurement capabilities.
  • Transformer Testing: Supports measurement of CT ratios, as well as CT and PT secondary burdens.

Product Features

  • User Interface: Features a 7-inch capacitive touchscreen supporting standalone operation. All electrical parameters are displayed on a single screen with a user-friendly HMI (Human-Machine Interface).
  • Intelligent Sensing: Automatically identifies connected current clamps without requiring manual range switching.
  • High Linearity: Provides wide-range linear measurement from 1% to 120% of the rated current.
  • Wireless Expansion: Supports the integration of wireless current clamps for measurements.
  • System Protection: Equipped with over-limit protection and wiring error protection.
  • Manual Audit Mode: Features a manual wiring analysis tool where users can input voltage, current, and phase data to diagnose errors, serving as a skill-enhancement tool for operators.
  • Connectivity: Includes USB, RS232, and Ethernet ports for PC data interaction and local/remote firmware upgrades.
  • Efficiency: Capable of measuring three-phase CT and PT burdens simultaneously, significantly reducing transformer testing time.

Technical Specifications

  • Accuracy Class: Class 0.05;
  • Voltage Input: Ranges: 100V, 200V, 400V;  Accuracy: Class 0.05 within 30V~500V;
  • Direct Current Input:  Accuracy Class: 0.05 for 0.5%~120%;
  • Clamp-on Input: Standard 5A clamps (Class 0.2 within ). Optional 100A, 500A, 1000A, and 3000A clamps available.
  • Power Measurement Accuracy: Class 0.05 (Direct input), Class 0.2 (Clamp input);
  • Power Supply: (Local power adapters available).
  • Power Source: Direct line power, power adapter, or optional battery.
  • Dimensions: ≤316mm × 265mm × 92mm;
  • Main Unit Weight: ≤1.8kg.

Standard Delivery Package

No. Item Specification Quantity
1 Main Unit T203C Main Unit 1 Set
2 Direct Input Module 0-5A, Class 0.05 1 Unit
3 Clamp Meter Module 5A Wired Clamp Meters (Standard, 3 units) 1 Set
5A Wireless Clamp Meter Optional
50A/100A/500A Clamp Meter (Wired or Wireless)
1000A Wireless High-Voltage Clamp Meter
4 Power Adapter T203C Power Adapter 1 Set
5 Accessories voltage test leads, pulse cables, meter-reading cables, and optical sampling cable sets. 1 Set
6 Documentation Packing list, Certificate, Manual, Test report, Warranty card 1 Set

Function Configuration List

Function Main Unit Voltage Leads Current Clamp Meter
5A 50A 100A 500A
Standard Electrical Parameter Measurement
Vector Diagram Display
Harmonic Measurement & Waveform Display
Error Verification
Metering Installation Error Verification
Wiring Error Analysis
Energy Retroactive Compensation for Incorrect Wiring
Dial Test Error (Energy Check)
CT Ratio
CT Secondary Burden
PT Secondary Burden
Notes:
● indicates Standard accessories.
○ indicates Optional accessories.